staging: comedi: amplc_pc263: Correct initial state
The initial state of the relays is being read incorrectly. It's reading a single 8-bit port twice, but should be reading two consecutive 8-bit ports. Fix it. Signed-off-by: Ian Abbott <abbotti@mev.co.uk> Signed-off-by: Greg Kroah-Hartman <gregkh@linuxfoundation.org>
This commit is contained in:
parent
a46e759fc0
commit
9f989000b5
@ -330,8 +330,7 @@ static int pc263_attach(struct comedi_device *dev, struct comedi_devconfig *it)
|
||||
/* all outputs */
|
||||
s->io_bits = 0xffff;
|
||||
/* read initial relay state */
|
||||
s->state = inb(dev->iobase);
|
||||
s->state = s->state | (inb(dev->iobase) << 8);
|
||||
s->state = inb(dev->iobase) | (inb(dev->iobase + 1) << 8);
|
||||
|
||||
printk(KERN_INFO "comedi%d: %s ", dev->minor, dev->board_name);
|
||||
switch (thisboard->bustype) {
|
||||
|